SM8001
Magnetic-inductive flow meter
SMR11GGXFRKG/US-100
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — SM8001-03 — 13.04.2023 —
Inputs
Inputs
counter reset
Outputs
Total number of outputs
2
Output signal
switching signal; analogue signal; pulse signal; IO-Link; (configurable)
Electrical design
PNP/NPN
Number of digital outputs
2
Output function
normally open / normally closed; (parameterisable)
Max. voltage drop switching
output DC
[V]
2
Permanent current rating of
switching output DC
[mA]
200
Number of analogue outputs
1
Analogue current output [mA]
4...20; (scalable)
Max. load [Ω]
500
Analogue voltage output [V]
0...10; (scalable)
Min. load resistance [Ω]
2000
Pulse output
flow rate meter
Short-circuit protection
yes
Type of short-circuit
protection
pulsed
Overload protection
yes
Measuring/setting range
Measuring range 6...1584 gph 0.1...26.4 gpm
Display range -1902...1902 gph -31.7...31.7 gpm
Resolution 2 gph 0.05 gpm
Set point SP 14...1586 gph 0.25...26.4 gpm
Reset point rP 6...1578 gph 0.1...26.25 gpm
Analogue start point ASP 0...1272 gph 0...21.2 gpm
Analogue end point AEP 312...1586 gph 5.2...26.4 gpm
In steps of 2 gph 0.05 gpm
Volumetric flow quantity monitoring
Pulse value
0.01...100 000 000 gal
Pulse length [s]
0,0025...2
Temperature monitoring
Measuring range [°F]
-4...176
Resolution [°F]
0.5
Set point SP [°F]
-2.5...176
Reset point rP [°F]
-3.5...175
Analogue start point [°F]
-4...140.5
Analogue end point [°F]
31.5...176
In steps of [°F]
0.5